Ginde Plastic Pipe Industry
|
|
| |
|
|
|
|

|

|
Click to enlarge image
|
Specifications of PVC-U Insulating Conduit Pipe
|
Nominal Size (mm) |
Outside Diameter (mm) |
Tolerance (mm) |
Min of Inside Diameter (mm) |
Min of Wall Thickness of Solid Conduit (mm) |
Length of Solid Conduit L(m) |
|
Solid Conduit |
Solid Conduit |
|
16 |
16 |
0 -0.3 |
12.2 |
1.0 |
4+0.005/0 Can Confirm With the Requirements of Transportation and Engineering. |
|
20 |
20 |
0 -0.3 |
15.8 |
1.1 |
|
25 |
25 |
0 -0.4 |
20.6 |
1.3 |
|
32 |
32 |
0 -0.4 |
26.6 |
1.5 |
|
40 |
40 |
0 -0.4 |
34.4 |
1.9 |
|
50 |
50 |
0 -0.5 |
43.2 |
2.2 |
|
63 |
63 |
0 -0.6 |
57.0 |
2.7 |
Technical Requirements of PVC-U Electrical Insulation Conduit and Fittings
|
No. |
Item |
Solid Conduit |
Fitting |
|
1 |
Appearance |
-(0.1+0.1A)≤⊿A≤(0.1+0.1A) |
Smooth,No Crack |
|
2 |
Max Diameter(outside) |
the Steel Ball can Go through the Pipe by Itself |
|
|
3 |
Min Diameter(outside) |
the Steel Ball can Go through the Pipe by Itself |
|
|
4 |
Min Diameter(inside) |
the Steel Ball can Go through the Pipe by Itself |
|
|
5 |
Min Wall Thickness |
Not Less Than the Required Wall Thickness |
|
|
6 |
Press Resistance (changing rate of outside diameter-%) |
Load of 1 min≤25 Unload of 1 min≤10 |
|
|
7 |
Impact Property |
10 of 12 Testing Pieces Shouldn't Damage at Least |
|
|
8 |
Flattening Property |
Invisible Crack |
|
|
9 |
Flexural Property |
the Steel Ball can Go through the Pipe by Itself |
|
|
10 |
Heat Resistance |
No Crack and Breakage |
No Crack and Breakage |
|
11 |
Drop Property |
Di≤2mm |
Di≤2mm |
|
12 |
Flame Resistance |
Self-extinguish Time |
te≤30s |
te≤30s |
|
Oxygen Index |
OI≥32 |
OI≥32 |
|
13 |
Electrical Property |
No Damage within 15min,R≥100MΩ |
No Damage Within 15min, R≥100MΩ |
|
|
|
|
| |
|
|
|